Equipment selection for Hvac Design such AHU Cooling Towers chillers etc..
let’s go step-by-step through the complete HVAC equipment selection procedure (AHU, chiller, cooling tower, etc.) using a commercial building project as an example.
🔷 Example Project Summary
Building: 10-story commercial office tower
Built-up area: 20,000 m² (approx. 215,000 ft²)
Location: Hot & humid climate (e.g., Dubai / Mumbai / Houston)
Function: Office spaces, meeting rooms, cafeteria, lobby, data room
System type: Central chilled water system with Air Handling Units (AHUs), Fan Coil Units (FCUs), chillers, cooling towers, and pumps.
🧩 Step-by-Step HVAC Equipment Selection Procedure
Step 1: Load Estimation
Objective: Determine the total cooling (and heating, if required) load for the building.
Procedure:
Collect Architectural & Engineering Data:
Floor plans, elevations, sections
Wall, roof, and glass types (U-values, shading)
Occupancy, lighting, and equipment density
Orientation and location (for weather data)
Ventilation & fresh air requirements (ASHRAE 62.1)
Calculate Cooling Load Components:
External Loads: Solar, walls, roof, glass, infiltration
Internal Loads: People, lights, equipment
Ventilation Load: Fresh air latent & sensible
Miscellaneous: Elevator machine rooms, server rooms, etc.
Software Tools:
HAP (Carrier), Trace 3D+, Elite CHVAC, or manual (CLTD/CLF or RTS method)
Example Output:
Total Cooling Load = 1400 TR (Tons of Refrigeration)
Sensible heat ratio (SHR) = 0.78
Step 2: System Selection
Objective: Decide what type of HVAC system best suits the project.
Options:
All-air system (central AHU + ducting)
Air-water system (AHU + FCU)
Water system (chilled beams, etc.)
Packaged or split systems (for smaller areas)
Example Decision:
Use a Chilled Water System with:
Central Chiller Plant (water-cooled chillers)
AHUs for each floor zone
FCUs for cabins/server room
Cooling towers and primary-secondary pumping
Step 3: Zoning
Objective: Divide building into zones based on orientation, usage, and load patterns.
Example:
Zone Description Load (TR)
Zone 1 North-facing floors 200
Zone 2 South-facing floors 300
Zone 3 Interior zones 400
Zone 4 Lobby, cafeteria 150
Zone 5 Data room & misc. 50
Total 1100 TR (with diversity)
Step 4: Equipment Selection
A. Chiller Selection
Input Data:
Total cooling load: 1100 TR
Diversity factor: 0.9 → Design load = 990 TR
Chilled water: 44°F (6.7°C) supply / 54°F (12.2°C) return
Condenser water: 85°F (29°C) supply / 95°F (35°C) return
Select Chillers:
Type: Water-cooled centrifugal chillers
No. of chillers: 2 working + 1 standby
Capacity per chiller: 500 TR
COP ≈ 6.0 (or IPLV ~ 6.5)
Manufacturer: Trane / Carrier / Daikin / York
Power Requirement:
500 TR × 2 = 1000 TR actual
Power ≈ 0.6 kW/TR → 600 kW total
B. Cooling Tower Selection
Heat Rejection = Load + Compressor Work
= 1000 TR + (1000 / 6.0) = 1167 TR ≈ 4.1 MW
Select Cooling Tower:
Type: Induced draft counterflow
Water flow rate: 3 gpm/TR → 3000 gpm
Temperature range: 95°F → 85°F
Approach: 7°F
No. of cells: 3 (each 400 TR)
Material: FRP or galvanized steel
C. Pumps Selection
Chilled Water Pump:
Flow rate = 2.4 gpm/TR → 2400 gpm
Head loss (estimated) = 70 ft
Power ≈ 60 HP per pump
Configuration: Primary (2 duty + 1 standby), Secondary (2 duty + 1 standby)
Condenser Water Pump:
Flow rate = 3.0 gpm/TR → 3000 gpm
Head loss = 60 ft
Power ≈ 75 HP per pump
D. Air Handling Units (AHUs)
Determine AHU requirements per zone:
Based on floor-wise loads.
Floor Load (TR) Airflow (CFM @ 400 CFM/TR) AHU Size
1–3 150 TR 60,000 CFM 3 AHUs of 20 TR each
4–7 200 TR 80,000 CFM 4 AHUs of 20 TR each
8–10 150 TR 60,000 CFM 3 AHUs of 20 TR each
Total 500 TR 200,000 CFM 10 AHUs
Select AHUs:
Cooling coil: 6-row chilled water
Face velocity: 450–500 fpm
Filter: MERV 8 pre + MERV 13 final
Fan type: Backward-curved plug fans (VFD-driven)
Supply air temp: 55°F (12.8°C)
E. Fan Coil Units (FCUs)
Small zones / cabins / data rooms.
Typical capacity: 1–5 TR each.
Supply: 44°F chilled water.
Return air & fresh air through separate ducts.
Step 5: Ducting and Piping Design
Design air ducts based on velocity (main duct ~1500 fpm, branch ~800 fpm)
Calculate static pressure for fan selection
Design chilled/condenser water piping (use friction loss 2–4 ft/100 ft)
Include balancing valves, strainers, expansion tanks, etc.
Step 6: Controls & BMS Integration
Chiller sequencing
VFD control for pumps and fans
AHU temperature & humidity control
Differential pressure sensors
Energy meters and performance monitoring
Step 7: Equipment Schedule (Summary Example)
Equipment Quantity Capacity Remarks
Water-cooled chiller 3 500 TR each 2W + 1S
Cooling tower 3 400 TR each FRP type
CHW Pump 3 2400 gpm, 70 ft head 2W + 1S
Condenser Pump 3 3000 gpm, 60 ft head 2W + 1S
AHU 10 20 TR each VFD, CW coil
FCU 25 2–5 TR Ceiling mounted
Expansion tank 1 1000 L
Chemical dosing & makeup 1 set —
Step 8: Validation
Cross-check loads vs. equipment capacity.
Confirm flow rates, coil face area, air velocity, and noise levels.
Verify compliance with ASHRAE, SMACNA, and local energy codes.
Step 9: Documentation & Submission
HVAC Design Report
Equipment Data Sheets
Schedules and BOQ
Manufacturer Selections
Layout Drawings (plant room, AHU rooms, piping, ducts)
✅ Final Outcome:
A fully optimized HVAC system where each piece of equipment (AHU, chiller, pump, cooling tower) is selected based on accurate load, redundancy, energy efficiency, and maintainability.
A complete HVAC equipment selection record for a commercial project.
I’ve also included formulas and sample data for clarity.
🧾 HVAC Equipment Selection Template (Excel Format)
Sheet 1: Project Summary
Parameter Description Example
Project Name “ABC Commercial Tower”
Location Dubai
Total Built-up Area (m²) 20,000
Floors 10
Design Conditions Indoor: 24°C DB, 50% RH / Outdoor: 43°C DB, 28°C WB
System Type Water-cooled chilled water system
Cooling Load Software HAP v5.13
Total Calculated Cooling Load (TR) =SUM(Zones!C2:C10) 1,400
Diversity Factor 0.9
Design Load (TR) =B9*B10 1,260 TR
Sensible Heat Ratio (SHR) 0.78
Sheet 2: Zone Load Summary
Zone / Floor Area (m²) Load (TR) Sensible Load (TR) Latent Load (TR) Airflow (CFM) =Load*400 Notes
GF Lobby 2,000 150 120 30 60,000 High occupancy
Floors 1–3 6,000 300 240 60 120,000 South orientation
Floors 4–7 8,000 400 310 90 160,000 Mixed orientation
Floors 8–10 4,000 150 120 30 60,000 North orientation
Data Room 300 40 40 0 16,000 24x7 load
Cafeteria 500 50 40 10 20,000 High latent
Total 20,800 1,090 TR 870 220 436,000
Sheet 3: Chiller Selection
Item Parameter Unit Formula / Value Example
Design Load TR =‘Project Summary’!B11 1,260
No. of Chillers Nos. 3 (2W + 1S) 3
Capacity per Chiller TR =B2/B3 420
Type Water-cooled centrifugal
COP 6.0
Chilled Water Flow gpm =TR*2.4 1008
Condenser Water Flow gpm =TR*3.0 1260
Power Input kW =TR*(0.6) 252
Manufacturer Trane / Carrier / York
Notes Include VFDs and BMS interface
Sheet 4: Cooling Tower Selection
Parameter Unit Formula / Value Example
Heat Rejected TR =Load + (Load/COP) 1,260 + 210 = 1,470
Flow Rate gpm =Load*3.0 3,780
Temp Range °C 35 → 29
No. of Cells 3 (2W + 1S)
Cell Capacity TR =B2/B5 490
Type Induced Draft, FRP
Approach °C 4
Fan Power kW 15 per cell
Total Power kW =15*2 30
Notes Include drift eliminators & water saver
Sheet 5: Pump Selection
Pump Type Flow (gpm) Head (ft) Efficiency Power (HP) =FlowHead/(3960Eff) Qty Remarks
Chilled Water Primary 2,520 70 0.75 =252070/(39600.75)=59 2W+1S VFD driven
Chilled Water Secondary 2,520 60 0.80 =252060/(39600.8)=48 2W+1S VFD driven
Condenser Water Pump 3,780 60 0.80 =3,78060/(39600.8)=72 2W+1S Duty/standby
Sheet 6: AHU Selection
Zone/Floor Load (TR) Airflow (CFM) AHU Qty CFM/AHU Coil Type Fan Type Filter Supply Temp (°C) Notes
GF Lobby 150 60,000 3 20,000 6-row CW Plug Fan (VFD) MERV 13 13 With return fan
1–3 Floors 300 120,000 6 20,000 6-row CW Plug Fan MERV 13 13 Zonal AHUs
4–7 Floors 400 160,000 8 20,000 6-row CW Plug Fan MERV 13 13 –
8–10 Floors 150 60,000 3 20,000 6-row CW Plug Fan MERV 13 13 –
Total 1000 TR 400,000 20 AHUs
Sheet 7: FCU Selection
Room Load (TR) Airflow (CFM) Type Coil Qty Remarks
Meeting Rooms 3 1,200 Ceiling 4-row CW 5
Server Room 5 2,000 Floor 4-row CW 2 24x7 duty
Cabins 1 400 Ceiling 4-row CW 10
Total 17
Sheet 8: Summary of Equipment
Equipment Qty Capacity Flow (gpm) Power (kW) Type / Remarks
Water-cooled Chiller 3 420 TR 1008 252 Centrifugal, VFD
Cooling Tower 3 490 TR 1260 15 Induced Draft, FRP
CHW Pump (Primary) 3 2520 gpm 70 ft 44 Inline VFD
CHW Pump (Secondary) 3 2520 gpm 60 ft 36 VFD driven
Condenser Pump 3 3780 gpm 60 ft 55 VFD driven
AHU 20 20 TR each — — 6-row coil
FCU 17 1–5 TR — — 4-row coil
Expansion Tank 1 1000 L — — Bladder type
Chemical Dosing Unit 1 — — — For closed loop
Sheet 9: Notes & References
Section Standard / Reference
Load Calculation ASHRAE Handbook – Fundamentals
Ventilation ASHRAE 62.1
System Design ASHRAE 90.1, 2022
Ductwork SMACNA Duct Design Manual
Pumps Hydraulic Institute Standards
Water Quality ASHRAE 188 (Legionella)
Controls BMS integration, BACnet protocol
🧮 Optional Formulas (for Excel)
You can paste these directly into Excel:
=Load_TR*2.4 # Chilled water flow (gpm)
=Load_TR*3.0 # Condenser water flow (gpm)
=Flow_gpm*Head_ft/(3960*Eff) # Pump HP
=Load_TR*400 # Airflow (CFM)
=Load_TR*(1+1/COP) # Heat rejected (TR)
📦 Deliverables You Can Generate from This Template
Equipment data sheets (auto-fill from Excel)
BOQ (Bill of Quantities)
Schedules for drawings
Load reports
Selection justification sheets (for consultant approval)
Comments
Post a Comment